Back to top
Send SMS
+918045475874
Most Popular Products
Trust Stamp
Product Showcase

Automatic Burner Control Unit

Automatic Burner Control Unit

Product Details:

  • Product Type burner controllers
  • Material Standard
  • Operating Temperature -40 to +80 Celsius (oC)
  • Protection System Standard
  • Size Standard
  • Weight 610 Grams (g)
  • Warranty 1 Year
1 INR/Unit
X

Price And Quantity

  • 1 INR/Unit
  • 1 Unit

Product Specifications

  • 1 Year
  • Standard
  • 610 Grams (g)
  • burner controllers
  • Standard
  • -40 to +80 Celsius (oC)
  • Standard

Trade Information

  • Telegraphic Transfer (T/T)
  • Standard
  • Asia
  • Gujarat

Product Description

Features:
  • For directly ignited burners of unlimited capacity in continuous operation pursuant to EN 746-2
  • Continuous self-testing for faults
  • Immediate fault lock-out or restart following flame failure available as a switchable function
  • Flame control with UV sensor or ionization sensor
  • Diverse installation possibilities via holes or snap mechanism for DIN rail
  • Space-saving installation on site with IFD 258..I with integrated ignition
  • Display for program status and flame signal intensity
Application:
  • Automatic burner control unit IFD 258 ignites and monitors directly ignited industrial gas burners of unlimited capacity.
  • As a result of its fully electronic design it reacts quickly to various process requirements and is therefore also suitable for frequent cycling operation.
  • It can be used for atmospheric burners or forced draught burners in multiple burner applications
  • Where a central control system is used for pre-purge and for monitoring.
  • The burners may be modulating or stagecontrolled.
  • The automatic burner control is suitable for operation in grounded and ungrounded systems.
  • The program status and the level of the flame signal can be read directly from the unit.
  • The switch-off threshold can be set using a potentiometer.
  • The behaviour in the event of flame failure during operation can be selected using a switch.
  • Either an immediate fault lock-out or a restart occurs.
Forced Draught Burners:
  • Control: On/Off
  • Gas valve and air valve are activated simultaneously.
  • The burner is ignited and monitored by a single electrode.
  • In the event of a flame failure, an immediate fault lock-out occurs.
Two-stage Controlled Burner:
  • Control: On/Off or On/High/Low/Off
  • The burner BIO/BIC starts at low-fire rate.
  • Once the normal operating state is reached
  • The automatic burner control unit for continuous
  • Operation IFD 258 will release control.
  • The PLC can now pulse the air solenoid valve
  • VRR in order to control the capacity between high and low fire.
Modulating Controlled Burner:
  • Control: On/Off/continuous
  • The PLC uses the actuator IC 20 to move the air butterfly valve BVA to ignition position.
  • The burner BIO/BIC starts at low-fire rate.
  • Once the normal operating state is reached
  • The PLC uses the actuator IC 20 and the air butterfly valve BVA to control the burner capacity.
Mains voltage for grounded and ungrounded mains:
  • 200 V AC, -15/+10%, 50/60 Hz
  • 120 V AC, -15/+10%, 50/60 Hz
  • 100 V AC, -15/+10%, 50/60 Hz
  • 230 V AC, -15/+10%, 50/60 Hz

 


SHINE CLUSTER INDUSTRIES